This unit can meet the full-load power generation requirements of low-concentration biogas (CH4 ≥ 30%), with feature of high efficiency, low energy consumption, easy maintenance, and high reliability, meeting the needs of customers.

√: Standard
○: Option
x: Unavailable
Remark:
All rated data are based on the operation under ISO 8528-1, 1SO 3046, DIN6271 conditions, using typical fan sizes and transmission ratios.
The performance tolerance referenced by Holly is ±5%.
The prime power = the power under the available load to replace the main power grid. 10% overload is allowed for one hour of operation every 12 hours.
Standby power = The power available under variable load in the event of a failure in the main power grid, with a maximum of 500 hours per year. Overload is not allowed.
Rated power factor: 0.8
* Suggested gas filtration standards:
1. Hydrogen sulfide (H2S) < 200mg/Nm³.
2. The content of impurity particles is less than 30mg/Nm³.
3. The diameter of impurity particles is less than 5μm.
4. The water content in the gas is less than 20g/Nm³.
5. Gas temperature < 40℃.
Note: If the gas filtration meets the above conditions, it can effectively extend the service life of the generator set.